Flint Hills Resources Revealed Causes of Crude Oil Spill
Following the incident, the company drained, air-gapped and disconnected the sump line from the piping.
SEATTLE (Oil Monster): Flint Hill Resources has announced the findings of investigation conducted by a third-party consultant into a recent incident that spilled thousands of gallons of oil into Corpus Christi Bay. The spill had occurred at Flint Hills Resources' Ingleside terminal. The fracture at the 3-inch sump line had led to release of approximately 335 barrels or 14,000 gallons of oil.
RELATED NEWS:
Dayton Residents Raised Concerns Over Oil Spills
TC Energy Says Stress, Weld Fault Caused Keystone Oil Spill
According to the investigation findings, the sump line was not emptied after the terminal's Dock 5 pump was removed from service in June last year. The water held in the line expanded and fractured due to subfreezing temperatures. The liquid in the line drained out and resulted in crude oil backflow and discharge from the sump line, the company news release stated.
Following the incident, the company drained, air-gapped and disconnected the sump line from the piping. In addition, it conducted comprehensive review of overall terminal operations to address similar risks. Flint Hill Resources noted that it has decided to install leak detection capability at the site to detect vapors in the air.
However, the release did not provide details on how many people or animals were injured or exposed to the oil.